Maximum dimensions (mm): instrument: 96 X 96 X 115.4. Cut-out template: 91 X 91
Power supply: switching circuit from 90V to 230V ±15% AC/DC @ 35-400 Hz (5 VA).
Display: reverse red LCD with LED backlight
Voltmeter inputs: VL1, VL2, VL3, N up to 350 V phase-neutral, 600 V phase-to-phase, 35-400 Hz
Voltmeter input impedance: 2 Mohm
Voltage input overload: max 850 V phase-neutral
Current inputs: AL1, AL2, AL3, COM., consumption 1 VA. Three or two 5A external curr.transf. required
Measuring range: 0-120% In
Sensitivity: current 20 mA ; voltage 10 mV
Overcurrent: withstand 50 amps for 1 sec.
Number of scales: 1 voltage scale, 2 current scales
Measurements: True R.M.S. up to 25th harmonic = 1250Hz with fundamental @50 Hz
Sampling frequency: 2.5 kHz.
Accuracy: <0.5% for Voltage and current and Power
Connection: Single phase or three phase star, three phase delta, or diphase systems
Weight: 0.6 Kg
Protection level: instrument IP20, front panel IP40
Temperature range: -10°C to +50°C
Relative humidity range: (R.H.): from 20% to 90%.
Condensation: non condensing. |